Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 710378.015
Citation: 01001
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $5,500.00
Current Penalty: $3,000.00
Issuance Date: 04/15/2013
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity:
Report ID: 0418300
Contest Date: 05/06/2013
Final Order: 02/07/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | J: ALJ Decision | 02/07/2014 | $3,000.00 | Other | ||
| Penalty | C: Contested | 05/09/2013 | $5,500.00 | Serious | ||
| Penalty | Z: Issued | 04/15/2013 | $5,500.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: (a) On or about 10/15/12 - At the High Pressure Receivers, a main shut-off valve HV 621 (king valve) was not identified with a prominent sign as specified in International Institute of Ammonia Refrigeration (IIAR) Bulletin No. 109 10/97, section 4.10.3.
Translate