Violation Detail
Standard Cited: 19260404 B01 II Wiring design and protection.
Inspection Nr: 678138.015
Citation: 01001
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $1,600.00
Current Penalty: $1,600.00
Issuance Date: 01/08/2013
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 5
Report ID: 0215800
Contest Date:
Final Order: 02/22/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 01/08/2013 | $1,600.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection: a) South side of home, Dining room, on or about 9-25-12: Employees were operating various power tools, powered through extension cord plugged into a duplex receptacle that was not protected by a ground fault circuit interrupter (GFCI).