Standard Cited: 19100106 H04 IVA Flammable liquids.

Inspection Nr: 314586595

Citation: 01001

Citation Type: Serious

Abatement Status: X

Initial Penalty: $4,900.00

Current Penalty: $4,900.00

Issuance Date: 09/29/2010

Nr Instances: 1

Nr Exposed: 3

Abatement Date: 11/01/2010

Gravity: 10

Report ID: 0522500

Contest Date:

Final Order:

Related Event Code (REC):

Emphasis:



Text For Citation: 01 Item/Group: 001 Hazard: CHEMNEP

29 CFR 1910.106(h)(4)(iv)(a): Equipment was not designed and arranged to prevent the unintentional escape of liquids and vapors and to minimize the quantity escaping in the event of accidental release: a.In the process area, the employer did not ensure that vessel flanges and/or fittings such as, but not necessarily limited to, V-301 were re-torqued prior to the process start up thereby exposing employees to a fire hazard. On or about July 17, 2010, a fire occurred in the process area that was the result of a flange and/or fitting on or in the vicinity of vessel 301 that failed to contain flammable liquids which leaked to an ignition source.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close