Violation Detail
Standard Cited: 5A0001 OSH Act General Duty Paragraph
Inspection Nr: 313890139
Citation: 01001
Citation Type: Serious
Abatement Date: 04/12/2010 X
Initial Penalty: $3,000.00
Current Penalty: $2,250.00
Issuance Date: 02/08/2010
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): R
Gravity: 10
Report ID: 0420600
Contest Date:
Final Order:
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/01/2010 | $2,250.00 | 04/12/2010 | Serious | |
Penalty | Z: Issued | 02/08/2010 | $3,000.00 | 04/12/2010 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard: EXPLOSION
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not gas supply system". 2. Follow the 2009 edition of the NFPA 54 National Fuel Gas Code, Section 5.10.2 entitled "Protective Devices" which states that "Protective devices shall include but not limited to the following: (A) Check Valves. (B) Three way valves (of type that completely closes one side before starting to open the other side). (C) Reverse flow indicators controlling shutoff valves. (D) Normally closed air-actuated positive-shutoff pressure regulators. 3. Install monitoring sensor devices on the blowers and or throughout the blower room. 4. Ensure that abatement is certified and approved by a Professional Engineer or the equivalent.