Violation Detail
Standard Cited: 19100119 D02 IA Process safety management of highly hazardous chemicals.
Inspection Nr: 313796732
Citation: 01001
Citation Type: Serious
Abatement Status: X
Initial Penalty: $7,000.00
Current Penalty: $5,000.00
Issuance Date: 07/07/2010
Nr Instances: 1
Nr Exposed: 226
Abatement Date: 08/23/2010
Gravity: 10
Report ID: 0111400
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/30/2010 | $5,000.00 | 08/23/2010 | Serious | |
| Penalty | Z: Issued | 07/07/2010 | $7,000.00 | 08/23/2010 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard: CHEMNEP
29 CFR 1910.119(d)(2)(i)(A): Process safety information pertaining to the technology of the process did not include a block flow diagram or simplified process flow diagram: Facility: The employer failed to include all main flow streams of the ammonia refrigeration system in the block flow diagram: a)flow of ammonia from Machine #11 high pressure receiver to the Machine #10 vertical flash accumulator to the Machine #9 low pressure receiver/processing pump package; b)flow of ammonia from Machine #12 low pressure receiver/storage pump package to evaporators in the old and new cold storage freezers, north and south coolers, bread & batter cooler, Chester Jensen falling film chiller, and office air conditioning chiller; and c)flow of ammonia from the condensers Machine #12 low pressure receiver/storage pump package.