Powered by GoogleTranslate

Violation Detail

Standard Cited: 5A0001 OSH Act General Duty Paragraph

Inspection Nr: 313784779

Citation: 01001

Citation Type: Serious

Abatement Status: X

Initial Penalty: $2,250.00

Current Penalty: $2,250.00

Issuance Date: 01/12/2011

Nr Instances: 1

Nr Exposed: 10

Abatement Date: 02/14/2011

Gravity: 05

Report ID: 0524700

Contest Date: 03/11/2011

Final Order: 01/17/2012

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty J: ALJ Decision 01/17/2012 $2,250.00 02/14/2011 Serious  
Penalty Z: Issued 01/12/2011 $2,250.00 02/14/2011 Serious  

Text For Citation: 01 Item/Group: 001 Hazard: BURNS

Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees, in that the natural gas fired burners in the Cuprite oven located in the North Foundry were not equipped with combustion safeguards that shut off the flow of fuel gas if the burner flame is extinguished: a.Chase Brass & Copper Company LLC located in Montpelier, Ohio: On or about September 7, 2010, the employer did not ensure the Cuprite oven located in the North Foundry was equipped with combustion safeguards. The natural gas is piped through the building, flows through a regulator and then is directed into each side of the furnace where it is ignited. Among other methods, one feasible and acceptable method to correct this hazard is to equip the furnace with combustion safeguards according to NFPA 86, Standard for Ovens and Furnaces 2011 edition. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation ( using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.