Violation Detail
Standard Cited: 19100036 E02 Design and construction requirements for exit routes.
Inspection Nr: 311796635
Citation: 01001
Citation Type: Serious
Abatement Date: 04/16/2010 Q
Initial Penalty: $1,700.00
Current Penalty: $850.00
Issuance Date: 06/08/2010
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 05
Report ID: 0112000
Contest Date:
Final Order:
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/24/2010 | $850.00 | 04/16/2010 | Serious | |
Penalty | Z: Issued | 06/08/2010 | $1,700.00 | 04/16/2010 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard: CHEMNEP
29 CFR 1910.36(e)(2): Exit door(s) did not swing out in the direction of travel when the room was designed to be occupied by more than 50 people or it the room was a high hazard area: Refrigeration System Mechanical Room: The front exit door opened into the room and was provided with a door knob. Abatement Note: The International Institute for Ammonia Refrigeration (IIAR) Standard 2 requires exit doors from mechanical rooms to swing in the direction of travel, be provided with panic hardware and be self- closing. Abatement Certification is Not Required