Violation Detail
Standard Cited: 95012901
Inspection Nr: 309413607
Citation: 01001
Citation Type: Serious
Abatement Status: X
Initial Penalty: $2,450.00
Current Penalty: $1,715.00
Issuance Date: 07/12/2006
Nr Instances: 1
Nr Exposed: 8
Abatement Date: 07/17/2006
Gravity:
Report ID: 0453710
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/17/2006 | $1,715.00 | 07/17/2006 | Serious | |
| Penalty | Z: Issued | 07/12/2006 | $2,450.00 | 07/17/2006 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard: ELECTRIC
North Carolina General Statute 95-129(1) of the Occupational Safety and Health Act of North Carolina: The employer did not furnish each of his employees conditions of employment and a place of employment free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to electrical hazards: a)establishment, kitchen meat preparation area - where equipment such as, but not limited to, a Hobart Chopper (model # 841810, Serial # 11253419, 11.1 amps, 115 VAC) was plugged into a receptacle which was not equipped with a Ground Fault Circuit Interrupter (GFCI). Abatement Note: One feasible and acceptable abate method, among others, to correct this hazard is to install Ground Fault Circuit Interrupters. [Reference: National Electrical Code 2005 Edition. NFPA 70, Article 210.9 (B)(2)]