Violation Detail
Standard Cited: 5A0001 OSH Act General Duty Paragraph
Inspection Nr: 308405158
Citation: 01001
Citation Type: Serious
Abatement Date: 08/23/2005 X
Initial Penalty: $1,875.00
Current Penalty: $1,875.00
Issuance Date: 05/24/2005
Nr Instances: 1
Nr Exposed: 130
Related Event Code (REC):
Gravity: 03
Report ID: 0418800
Contest Date:
Final Order:
Emphasis:
Text For Citation: 01 Item/Group: 001 Hazard: UNAPEQUIP
Section 5(a)1 of the Occupational Safety and Health Act of 1970: The employer did not furnish to each of his employees employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to anhydrous ammonia refrigerant: (a)On or about 05/19/05, the processing ammonia refrigeration system did not meet requirements for the safe design, construction, installation, and operation as presented in ANSI/ASHRAE Standard 15-2001, Safety Standard for Refrigeration Systems, in that the receiver's pressure relief devices did not discharge to the atmosphere at a location at least 15 feet (4.57 meters) above the adjoining ground level (ANSI/ASHRAE 15-2001, Section 9.7.8.2). A feasible and acceptable abatement method is to plumb the safety valve discharge to at least 15 feet above ground level. PLEASE NOTE: DOCUMENTATION AND CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.ION