Violation Detail
Standard Cited: 19100106 D04 IV Flammable liquids.
Inspection Nr: 280114.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/31/2012
Nr Instances: 2
Nr Exposed: 5
Abatement Date: 09/24/2012
Gravity: 5
Report ID: 0936200
Contest Date:
Final Order: 09/25/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 08/31/2012 | $0.00 | 09/24/2012 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(d)(4)(iv): An inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system that was designed to provide for a complete change of air within the room at least six times per hour: a) In Room 60 - On or about 3/7/12, the exhaust ventilation for the flammable storage room was capped in the penthouse. b) In Room 80 - On or about 3/7/12, the exhaust ventilation for the flammable storage room was non-functional.