Violation Detail
Standard Cited: 19100303 G01 I General.
Inspection Nr: 1849915.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,979.00
Current Penalty: $1,787.40
Issuance Date: 12/04/2025
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 12/31/2025
Gravity: 1
Report ID: 0420600
Contest Date:
Final Order: 03/23/2026
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/23/2026 | $1,787.40 | 12/31/2025 | Serious | |
| Penalty | Z: Issued | 12/04/2025 | $2,979.00 | 12/31/2025 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1)(i):The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1: (a) In the X-Ray Room, located at 4424 Friendly Way, Wesley Chapel, FL 33543, on or about 9/11/2025, the employer exposed employees to electrical hazards, in that the 125 kV InnoVet X-Ray machine was placed directly in front of the disconnect, preventing its access by employees.