Standard Cited: 19100305 G01 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1845676.015
Citation: 01001
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $8,512.00
Current Penalty: $6,384.00
Issuance Date: 02/12/2026
Nr Instances: 3
Nr Exposed: 1
Abatement Date:
Gravity: 1
Report ID: 0317900
Contest Date:
Final Order: 03/27/2026
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/27/2026 | $6,384.00 | Serious | ||
| Penalty | Z: Issued | 02/12/2026 | $8,512.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.305(g)(1)(iii):Flexible cords and cables were used for purposes prohibited by subparagraphs (A) through (E) of this paragraph: a) 200 West 7th Ave, Collegeville, ECM and Fab area rear exit door - Employees are performing work tasks in a shop area that contains flexible cords used for permanent wiring. Energized extension cord secured to building's structure, over a pedestrian walkway, powering a vending machine on the other side. b) 200 West 7th Ave, Collegeville, ECM and Fab area rear exit door - Employees are performing work tasks in a shop area with flexible cords utilized for permanent wiring. Energized extension cord is run from a hallway between a door and frame, into another room to power a scale. c) 200 West 7th Ave, Collegeville, ECM and Fab area - Employees are performing work tasks in a shop area with flexible cords utilized for permanent wiring. An energized extension cord is secured to overhead building members and powers a machine that dispenses personal protective equipment.
Translate