Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1840258.015
Citation: 01001
Citation Type: Other
Abatement Status: Quick Fix
Initial Penalty: $8,199.00
Current Penalty: $6,500.00
Issuance Date: 12/08/2025
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 04/09/2026
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 04/09/2026 | $6,500.00 | Other | ||
| Penalty | Z: Issued | 12/08/2025 | $8,199.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Electrical Room: On, or about, July 29, 2025, circuit 14, a lighting circuit for Suite 202, was not properly labeled. The legend for the General Electric Series A panelboard indicated that the circuit was a spare.