Violation Detail
Standard Cited: 19100137 C02 XII Electrical protective equipment.
Inspection Nr: 1823315.015
Citation: 01001
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $11,823.00
Current Penalty: $7,093.80
Issuance Date: 07/21/2025
Nr Instances: 1
Nr Exposed: 1
Abatement Date:
Gravity: 5
Report ID: 0419730
Contest Date:
Final Order: 08/12/2025
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/12/2025 | $7,093.80 | Serious | ||
| Penalty | Z: Issued | 07/21/2025 | $11,823.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.137(c)(2)(xii): The employer did not certify that equipment has been tested in accordance with the requirements of paragraphs (c)(2)(iv), (c)(2)(vii)(D), (c)(2)(viii), (c)(2)(ix), and (c)(2)(xi) of this section. a) On or about May 8, 2025, Electrical room in Deli portion of the warehouse: an employee was exposed to ARC flash hazards, in that, a pair of NOVAX Class 0, 1000 volt rated gloves had not been inspected since December 7, 2023. b) On or about May 8, 2025 , Electrical room in Deli portion of the warehouse: an employee was exposed to ARC flash hazards, in that , a MAGID PowerMaster 12501PS leather lineman glove was not inspected since August 17, 2023. c) On or about May 8, 2025 , Electrical room in Deli portion of the warehouse: an employee was exposed to ARC flash hazards, in that , Chicago Protection Apparel item: SWJ-12-XL protective jacket, was not inspected since March 2, 2021. d) On or about May 8, 2025 , Electrical room in Deli portion of the warehouse: an employee was exposed to ARC flash hazards, in that, Chicago Protective Apparel Model# AMP12RWHTS-EC ARC Flash Protective Shield was not inspected since March 2, 2021.
Translate