Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
Inspection Nr: 1734233.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,803.00
Current Penalty: $1,901.50
Issuance Date: 08/22/2024
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 10/22/2024
Gravity: 5
Report ID: 0112300
Contest Date:
Final Order: 09/17/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/17/2024 | $1,901.50 | 10/22/2024 | Serious | |
Penalty | Z: Issued | 08/22/2024 | $3,803.00 | 10/08/2024 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons of Category 2, 3, or 4 flammable liquids in containers. (a) Facility at 310 Bourne Avenue (building 50) in Rumford, RI: On or about March 13, 2024, employees working in the shop area were exposed to fire and burn hazards from inadequate storage of flammable liquids including, but not limited to, two (2) 55 - gallon drums of 8040 MVP with a flashpoint of 89 degrees F, approximately 33 cans of spray paint such as MTN, approximately 50 gallon containers of various flammable liquids such as AwlGrip and Alexseal topcoats, reducers, converters, primers, strippers, cleaners, and bases.