Violation Detail
Standard Cited: 19100119 D03 I H Process safety management of highly hazardous chemicals.
Inspection Nr: 1696750.015
Citation: 01001
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $12,676.00
Current Penalty: $12,875.00
Issuance Date: 03/08/2024
Nr Instances: 1
Nr Exposed: 30
Abatement Date: 04/29/2024
Gravity: 5
Report ID: 0524500
Contest Date: 04/01/2024
Final Order: 04/17/2025
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 04/17/2025 | $12,875.00 | 04/29/2024 | Other | |
| Penalty | C: Contested | 04/03/2024 | $12,676.00 | 04/29/2024 | Serious | |
| Penalty | Z: Issued | 03/08/2024 | $12,676.00 | 04/29/2024 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(3)(i)(H): Process safety information pertaining to the equipment in the process did not include the safety systems (e.g., interlocks, detection or suppression systems): The employer failed to maintain accurate process safety information for the safety systems and interlocks on the raw flake conveyance systems to the Extractor. The process safety information documented a safety interlock for an air actuated slide gate at the discharge of the Extractor Plug Screw when conveying goes down although this piece of equipment was not interlocked to close when conveying was stopped.