Violation Detail
Standard Cited: 19100119 D03 I D Process safety management of highly hazardous chemicals.
Inspection Nr: 1663647.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,046.00
Current Penalty: $6,697.00
Issuance Date: 09/29/2023
Nr Instances: 3
Nr Exposed: 40
Abatement Date: 03/01/2024
Gravity: 5
Report ID: 0215800
Contest Date:
Final Order: 11/01/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 12/15/2023 | $6,697.00 | 03/01/2024 | Serious | |
Penalty | I: Informal Settlement | 11/01/2023 | $6,697.00 | 11/17/2023 | Serious | |
Penalty | Z: Issued | 09/29/2023 | $10,046.00 | 11/17/2023 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(3)(i)(D): Information pertaining to equipment in the process did not include relief system design and design basis: a) On or about 4/5/2023, Roof Condensers, Information pertaining to the use of pressure cut-out devices in lieu of pressure relief valves did not include relief system design and design basis. b) On or about 4/5/2023, Cellar K, K-Hops cooler, Information pertaining to the use of regulators in lieu of pressure relief valves did not include relief system design and design basis. c) On or about 4/5/2023, Throughout the Anhydrous Ammonia refrigeration system, the employer had not calculated for the pressure relief devices to release back into the low side of the system. Abatement documentation is required for these items.