Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
Inspection Nr: 1658515.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,679.00
Current Penalty: $1,875.30
Issuance Date: 06/29/2023
Nr Instances: 1
Nr Exposed: 7
Abatement Date: 12/15/2023
Gravity: 5
Report ID: 0523900
Contest Date:
Final Order: 07/25/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/25/2023 | $1,875.30 | 12/15/2023 | Serious | |
| Penalty | Z: Issued | 06/29/2023 | $2,679.00 | 10/02/2023 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquids located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons: (a) Production Areas; The quantity of Category 2, 3, and 4 flammables (i.e. DCPD Laminating Resin, White Gel Coat, MEKP, and Acetone), located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building, was approximately 1,210 gallons.