Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 1657024.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $15,625.00
Current Penalty: $15,625.00
Issuance Date: 07/13/2023
Nr Instances: 6
Nr Exposed: 625
Abatement Date: 08/15/2023
Gravity: 10
Report ID: 0420600
Contest Date:
Final Order: 08/07/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/07/2023 | $15,625.00 | 08/15/2023 | Serious | |
Penalty | Z: Issued | 07/13/2023 | $15,625.00 | 08/15/2023 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process. a) For engine room number 2-3 at the Coca-Cola Auburndale, FL site, on or about 3/16/23, a ? inch Hansen HGV1 Long Neck Service/Gauge Valve located on piping associated with suction accumulator V-33 and downstream of an 8-inch isolation/stop valve, RL-1, was not depicted on the employer?s piping and instrumentation diagrams. b) For engine room number 2-3 at the Coca-Cola Auburndale, FL site, on or about 3/16/23, pressure gauge at a ? inch service/gauge valve on piping associated with suction accumulator V-33 and downstream of an 8-inch isolation/stop valve, RL-1, was not depicted on the employer?s piping and instrumentation diagrams. c) For engine room number 2-3 at the Coca-Cola Auburndale, FL site, on or about 3/16/23, valve RL-1/CH-31 was incorrectly field-labeled with respect to piping and instrumentation drawing number V-33A. d) For engine room number 2-3 at the Coca-Cola Auburndale, FL site, on or about 3/16/23, five valves at high pressure receiver V23 had illegible valve tags for valves depicted on piping and instrumentation drawing number V-23. e) For engine room number 2-3 at the Coca-Cola Auburndale, FL site, on or about 3/16/23, chiller CH-31 and isolation/stop valve RL-1/V-33 were located on the wrong side of the suction accumulator V-33 with respect to the level column on the piping and instrumentation drawing number V-33A.