Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
This violation item has been deleted.
Inspection Nr: 1647295.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $15,625.00
Current Penalty: $0.00
Issuance Date: 08/02/2023
Nr Instances: 2
Nr Exposed: 2
Abatement Date: 09/06/2023
Gravity: 10
Report ID: 0626700
Contest Date: 08/14/2023
Final Order: 12/13/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 12/13/2023 | $0.00 | 09/06/2023 | Serious | |
Penalty | C: Contested | 09/18/2023 | $15,625.00 | 09/06/2023 | Serious | |
Penalty | Z: Issued | 08/02/2023 | $15,625.00 | 09/06/2023 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.107(c)(6): Electrical wiring, motors, and other equipment outside of but within twenty (20) feet of any spray area, and not separated therefrom by partitions, produced sparks under normal operating conditions and did not otherwise conform to the provisions of subpart S of this part for Class I, Division 2 Hazardous Locations: a) In the spray area on January 31, 2023, and times prior to, where the fluorescent lighting was exposed to combustible residue and not classified as explosion proof. b) In the spray area on January 31, 2023, and times prior to, where the flexible cords were exposed to combustible residue and not classified as explosion proof.