Violation Detail
Standard Cited: 19100159 C10 Automatic sprinkler systems.
Inspection Nr: 1618339.015
Citation: 01001
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $5,811.00
Current Penalty: $2,905.50
Issuance Date: 01/04/2023
Nr Instances: 1
Nr Exposed: 150
Abatement Date:
Gravity: 1
Report ID: 0522000
Contest Date:
Final Order: 01/25/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/25/2023 | $2,905.50 | Serious | ||
Penalty | Z: Issued | 01/04/2023 | $5,811.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.159(c)(10):Sprinkler spacing. The employer shall assure that sprinklers are spaced to provide a maximum protection area per sprinkler, a minimum of interference to the discharge pattern by building or structural members or building contents and suitable sensitivity to possible fire hazards. The minimum vertical clearance between sprinklers and material below shall be 18 inches (45.7 cm). a) On or about September 26, 2022 in the overflow area, paper products had been stored in two tiers which was above the sprinkler heads.