Violation Detail
Standard Cited: 19260403 I02 I General requirements.
Inspection Nr: 1610806.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,801.00
Current Penalty: $5,801.00
Issuance Date: 01/09/2023
Nr Instances: 3
Nr Exposed: 2
Abatement Date: 01/17/2023
Gravity: 10
Report ID: 0215000
Contest Date:
Final Order: 02/07/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 01/09/2023 | $5,801.00 | 01/17/2023 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50-volts or more were not guarded against accidental contact. Location: 754 Grand Street, Brooklyn, NY 11211 On or about 7/13/2022, a) At the west wall of a hallway on the ground floor, 110-volt live conductors protruding from junction boxes were not guarded from accidental contact by employees. b) At the east wall of a hallway on the ground floor, 110-volt live empty lightbulb sockets of the temporary lighting system were not guarded from accidental contact by employees. c) A breaker panel in the basement was missing the dead front cover. Live electrical parts of 110-volt were not guarded from accidental contact by employees.