Violation Detail
Standard Cited: 19100106 B04 IV G Flammable liquids.
Inspection Nr: 1597059.015
Citation: 01001
Citation Type: Other
Abatement Status: Not Completed - AD Discretion
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/15/2022
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 01/04/2023
Gravity:
Report ID: 0112000
Contest Date:
Final Order: 03/30/2023
Related Event Code (REC): C
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 11/15/2022 | $0.00 | 01/04/2023 | Other |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(b)(4)(iv)(g): The inlet of the fill pipe shall be located outside of buildings at a location free from any source of ignition and not less than 5 feet away from any building opening. The inlet of the fill pipe shall be closed and liquid-tight when not in use. The fill connection shall be properly identified. Maintenance garage at Cedar Ridge Golf Course: On or about May 19, 2022, the fill pipe provided on the 138-gallon fire pump tank was located inside the building. The tank contained diesel fuel, a Category 3 flammable liquid.