Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 1592816.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,360.00
Current Penalty: $10,360.00
Issuance Date: 10/20/2022
Nr Instances: 3
Nr Exposed: 14
Abatement Date: 01/30/2023
Gravity: 5
Report ID: 0728500
Contest Date: 11/15/2022
Final Order: 03/13/2023
Related Event Code (REC):
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/13/2023 | $10,360.00 | 01/30/2023 | Serious | |
Penalty | C: Contested | 11/17/2022 | $10,360.00 | 11/16/2022 | Serious | |
Penalty | Z: Issued | 10/20/2022 | $10,360.00 | 11/16/2022 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process. At a worksite located at 4600 Waco Rd, Columbia, MO 65202 (Ammonia Yard): a) This included but was not limited to ANSI/IIAR 2 - 2021 Section 5.14.6, when the ammonia piping system line B3 PHL HDP located in Powerhouse Yard on P&ID R706 was not labeled with the following information: "ammonia, physical state (e.g. liquid or gas), relative pressure level, and direction of flow. This hazardous condition exposed employees engaged in repairing, replacing, operating, inspecting, testing, and maintenance activities of covered process equipment to toxic, cryogenic, and fire hazards in the event of an anhydrous ammonia release.