Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1579232.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,594.00
Current Penalty: $5,594.00
Issuance Date: 04/01/2022
Nr Instances: 1
Nr Exposed: 7
Abatement Date: 04/07/2022
Gravity: 5
Report ID: 0418600
Contest Date:
Final Order: 04/28/2022
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 04/01/2022 | $5,594.00 | 04/07/2022 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(e)(6)(ii): Grounding. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), shall not be dispensed into containers unless the nozzle and container are electrically interconnected. Where the metallic floorplate on which the container stands while filling is electrically connected to the fill stem or where the fill stem is bonded to the container during filling operations by means of a bond wire, the provisions of this section shall be deemed to have been complied with. a) Ransburg #1-2 and Pre-Paint Booth waste container stations; On or about February 11, 2022, and at times prior thereto, the employer exposed employees to burn hazards in that employees were allowed to transfer a Class 2 flammable liquid from one container to another without both containers being electrically connected / grounded.