Violation Detail
Standard Cited: 19100304 B04 II B Wiring design and protection.
Inspection Nr: 1572848.015
Citation: 01001
Citation Type: Serious
Abatement Status: Quick Fix
Initial Penalty: $5,283.00
Current Penalty: $5,283.00
Issuance Date: 03/11/2022
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 04/07/2022
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 03/11/2022 | $5,283.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4: Storage Area: On, or about, January 13, 2022, a 15 ampere relocatable power tap was used to energize a DeWalt Model DW716 chop saw, a Metcal Model MX1 69470 soldering gun, a light and a label maker. The combined load of the devices exceeded the maximum load allowed on the relocatable power tap, which was 12 amperes.
Translate