Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1551976.015
Citation: 01001
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $4,973.00
Current Penalty: $2,984.00
Issuance Date: 10/18/2021
Nr Instances: 1
Nr Exposed: 1
Abatement Date:
Gravity: 1
Report ID: 0626700
Contest Date:
Final Order: 11/08/2021
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 11/08/2021 | $2,984.00 | Serious | ||
| Penalty | Z: Issued | 10/18/2021 | $4,973.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : a) At building #7, the width of the working space in front of the electrical power switches were less than 30 inches, exposing employees to electrical hazards.