Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1551176.015
Citation: 01001
Citation Type: Other
Abatement Date: 03/28/2022 2
Initial Penalty: $14,502.00
Current Penalty: $8,701.00
Issuance Date: 03/02/2022
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order: 03/29/2022
Emphasis:
Substance: 1650
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/29/2022 | $8,701.00 | 03/28/2022 | Other | |
Penalty | Z: Issued | 03/02/2022 | $14,502.00 | 03/28/2022 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), was dispensed into containers where the nozzle and container were not electrically interconnected: On or about September 2, 2021, in the contact department, employees dispensed glue from a 55-gallon drum of B688 Permagrip glue, a Category 3 Flammable Liquid that was not bonded or grounded to prevent fire and explosion hazards.