Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1540062.015
Citation: 01001
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/14/2022
Nr Instances: 1
Nr Exposed: 3
Abatement Date:
Gravity: 5
Report ID: 1032100
Contest Date:
Final Order: 02/23/2022
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 01/14/2022 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1)(i)(B): The width of working space in front of the electric equipment shall be the width of the equipment or 762 mm (30 in.), whichever is greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged panels. a) FAA ATCT Tracon/Tower: On and or about June 29, 2021, electrical panel was blocked with boxes and cleaning supplies exposing employees to electrical shock, fire hazards and a delay in emergency operations.