Violation Detail
Standard Cited: 19260404 B01 III C Wiring design and protection.
Inspection Nr: 1498699.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,181.00
Current Penalty: $3,181.00
Issuance Date: 11/03/2020
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 11/13/2020
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 12/02/2020
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 11/03/2020 | $3,181.00 | 11/13/2020 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.404(b)(1)(iii)(C): Each cord set, attachment cap, plug and receptacle of cord sets, and any equipment connected by cord and plug, except cord sets and receptacles which are fixed and not exposed to damage, shall be visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage. Equipment found damaged or defective shall not be used until repaired. a) Miguel Dominguez, at a jobsite located at 768 Wharncliff, Lot WEL138, Pickerington, Ohio 43062: On and/or preceding October 20, 2020, the employer did not ensure extension cords were visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage. Roofers were using a yellow extension cord with missing insulation along its length and a missing ground prong, which exposed the employees to a 123 volt electrical contact hazard.