Violation Detail
Standard Cited: 19100157 D04 Portable fire extinguishers.
This violation item has been deleted.
Inspection Nr: 1495912.015
Citation: 01001
Citation Type: Serious
Abatement Status:
Initial Penalty: $5,398.00
Current Penalty: $0.00
Issuance Date: 01/12/2021
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 02/08/2021
Gravity: 5
Report ID: 0729700
Contest Date:
Final Order: 02/04/2021
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/04/2021 | $0.00 | 02/08/2021 | Serious | |
| Penalty | Z: Issued | 01/12/2021 | $5,398.00 | 02/08/2021 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.157(d)(4): Portable fire extinguishers for use on Class B fires were not distributed so that the travel distance from the Class B hazard area to any extinguisher is 50 feet or less: Employees were exposed to fire hazards. Ottawa Cooperative Association's truck drivers were exposed to fire hazards. Portable fire extinguishers for use in Class B Fires were located approximately 78 feet away from a 2,000-gallon diesel tank used by the company's drivers.