Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1431565.015
Citation: 01001
Citation Type: Serious
Abatement Date: 10/28/2019 2
Initial Penalty: $3,978.00
Current Penalty: $2,500.00
Issuance Date: 10/01/2019
Nr Instances: 1
Nr Exposed: 3
Related Event Code (REC):
Gravity: 1
Report ID: 0830500
Contest Date:
Final Order: 10/10/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/10/2019 | $2,500.00 | 10/28/2019 | Serious | |
Penalty | Z: Issued | 10/01/2019 | $3,978.00 | 10/28/2019 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : (a) Green Hemp Farms, Inc. at 1760 Gunnison Ave. Delta, CO 81416: On or before 9/17/19 the employer did not protect employees from injury in that two electrical panels at 480V did not have at least thirty inches of clearance in front of the panel and were blocked by assorted tools, equipment and materials. This condition exposed employees to electric shock hazards.