Powered by GoogleTranslate

Violation Detail

Standard Cited: 19260417 B Lockout and tagging of circuits.

Inspection Nr: 1407771.015

Citation: 01001

Citation Type: Serious

Abatement Status: Abatement Completed

Initial Penalty: $9,282.00

Current Penalty: $5,569.20

Issuance Date: 12/10/2019

Nr Instances: 1

Nr Exposed: 5

Abatement Date: 01/07/2020

Gravity: 10

Report ID: 0419700

Contest Date:

Final Order: 01/14/2020

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty I: Informal Settlement 01/14/2020 $5,569.20 01/07/2020 Serious  
Penalty Z: Issued 12/10/2019 $9,282.00 01/07/2020 Serious  

Text For Citation: 01 Item/Group: 001 Hazard:

29 CFR 1926.417(b): Equipment or circuits that were de-energized did not have tags attached at all points where such equipment or circuits could be energized: a. On or about June 6, 2019, at the Dolphin Pointe Health Care building construction job site, in the first-floor electrical panel room with temporary electrical power supplied, the employer exposed 5 electrician employees to 277-Volt shock hazards in that deenergized electrical circuits did not have tags at all points where equipment and circuits could be energized while employees were working on the wiring.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.