Violation Detail
Standard Cited: 19260150 C01 VI Fire protection.
Inspection Nr: 1394710.015
Citation: 01001
Citation Type: Serious
Abatement Status: Quick Fix
Initial Penalty: $2,874.00
Current Penalty: $2,155.50
Issuance Date: 07/17/2019
Nr Instances: 1
Nr Exposed: 6
Abatement Date:
Gravity: 1
Report ID: 0317900
Contest Date:
Final Order: 07/29/2019
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/29/2019 | $2,155.50 | Serious | ||
| Penalty | Z: Issued | 07/17/2019 | $2,874.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.150(c)(1)(vi): A fire extinguisher, rated not less than 10B, was not provided within 50 feet of wherever more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas were being used on the jobsite: a) Construction site, Wrightstown Elementary, Roof - On or about April 12, 2019, the fire extinguisher positioned on the roof where employees applying hot patches on the roof used propane torches had been previously discharged.