Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1386295.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,260.00
Current Penalty: $13,260.00
Issuance Date: 05/14/2019
Nr Instances: 2
Nr Exposed: 52
Abatement Date: 12/31/2019
Gravity: 10
Report ID: 0418100
Contest Date:
Final Order: 06/11/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | $13,260.00 | 12/31/2019 | Serious | ||
Penalty | Z: Issued | 05/14/2019 | $13,260.00 | 07/01/2019 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. On 3/19/19, at the Suwanee facility, the employer did not ensure equipment pertaining to the Ammonia refrigeration system complied with recognized and generally accepted good engineering practices. Instances included: a - Engine room Ammonia alarms were not set correctly and in accordance with ANSI/IIAS 2-2104. b - There were no audible or visual alarms at each entrance of the engine room and in accordance with ANSI/IIAS 2-2104.