Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
This violation item has been deleted.
Inspection Nr: 1379680.015
Citation: 01001
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $7,293.00
Current Penalty: $0.00
Issuance Date: 08/12/2019
Nr Instances: 1
Nr Exposed: 1
Abatement Date:
Gravity: 5
Report ID: 0523400
Contest Date:
Final Order: 08/21/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/21/2019 | $0.00 | Serious | ||
Penalty | Z: Issued | 08/12/2019 | $7,293.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(e)(6)(ii): Grounding. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 degrees F (37.8 degrees C), shall not be dispensed into containers unless the nozzle and container are electrically interconnected. Where the metallic floorplate on which the container stands while filling is electrically connected to the fill stem or where the fill stem is bonded to the container during filling operations by means of a bond wire, the provisions of this section shall be deemed to have been complied with. a. On or about 2/21/2019 three 55 gallon drums of a class 1 flammable liquid (mineral oil) were not grounded or bonded during filling operations by means of a bond wire.