Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
Inspection Nr: 1331518.015
Citation: 01001
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/15/2019
Nr Instances: 1
Nr Exposed: 350
Abatement Date:
Gravity: 5
Report ID: 0316700
Contest Date:
Final Order: 02/11/2020
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 01/15/2019 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons: (a) NORTH EXTERIOR OF PAINT KITCHEN, BUILDING 350 - The employer staged for use three (3) 55 gallon drums of Tan 686A paint (category 2 flammable liquid) and two (2) 55 gallon drums of Epoxy Hardener Part B (category 3 flammable liquid) near the exterior of the North Side of the paint kitchen. Also staged in the near vicinity were two (2) 55 gallon drums of MIL-T--81772b T1 Polyurethane Reducer (category 2 flammable liquid) and three 55 gallon drums of liquid paint waste (category 2 flammable liquid). The total quantity of combined category 2 and category 3 flammable liquids not properly stored totaled 550 gallons, on or about July 19, 2018. No abatement certification or documentation required.