Violation Detail
Standard Cited: 19260404 B01 I Wiring design and protection.
Inspection Nr: 1320364.015
Citation: 01001
Citation Type: Other
Abatement Date: 08/11/2020 2
Initial Penalty: $3,880.00
Current Penalty: $1,940.00
Issuance Date: 11/29/2018
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): A
Gravity:
Report ID: 0729300
Contest Date: 12/19/2018
Final Order: 05/11/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 05/11/2020 | $1,940.00 | 08/11/2020 | Other | |
Penalty | C: Contested | 12/20/2018 | $3,880.00 | 12/20/2018 | Serious | |
Penalty | Z: Issued | 11/29/2018 | $3,880.00 | 12/20/2018 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.404(b)(1)(i): The employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. The employer is failing to protect employees from an electrocution hazard. The suspended scaffold was powered by a 208volt electric SPIDER motor that was not equipped with ground fault protection or assured grounding program.