Violation Detail
Standard Cited: 19100305 E01 Wiring methods, components, and equipment for general use.
Inspection Nr: 1299150.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,934.00
Current Penalty: $9,053.80
Issuance Date: 05/17/2018
Nr Instances: 2
Nr Exposed: 6
Abatement Date: 06/13/2018
Gravity: 10
Report ID: 0521700
Contest Date:
Final Order: 06/19/2018
Related Event Code (REC): C
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/19/2018 | $9,053.80 | 06/13/2018 | Serious | |
| Penalty | Z: Issued | 05/17/2018 | $12,934.00 | 06/13/2018 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures. In wet locations the enclosure was not weatherproof: a) In the scullery/garbage disposal/tray conveyor area - On or about March 5, 2018, at the above located workplace employees were required to work with and around a 208 Volt, 3 phase, garbage disposal control box that had a cover which was not properly sealed and an unused opening in the side of the control box. The garbage disposal control box with the unsealed cover and the unused opening in its side was unsuitable for the wet and/or damp location. Employees were thereby exposed to electrical hazards. b) In the scullery/garbage disposal/tray conveyor area - On or about March 5, 2018, at the above located workplace employees were required to work with and around a flexible conduit that was disconnected from a 120 volt food tray conveyor drive motor. The lack of a proper connection would allow water to enter the motor and made the equipment unsuitable for the damp and/or wet location. Employees were thereby exposed to electrical hazards.
Translate