Violation Detail
Standard Cited: 19100023 B02 Ladders.
Inspection Nr: 1272570.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,464.00
Current Penalty: $4,524.80
Issuance Date: 11/07/2017
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 01/02/2018
Gravity: 5
Report ID: 0418300
Contest Date:
Final Order: 12/04/2017
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | P: Petition to Mod Abatement | $4,524.80 | 01/02/2018 | Serious | ||
| Penalty | I: Informal Settlement | 12/04/2017 | $4,524.80 | 01/02/2018 | Serious | |
| Penalty | Z: Issued | 11/07/2017 | $6,464.00 | 12/05/2017 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.23(b)(2): Ladder rungs, steps, and cleats were not spaced less than 10 inches (25 cm) and not more than 14 inches (36 cm) apart, as measured between the centerlines of the rungs, cleats, and steps: (a) On or about 10/17/2017 - Roof top HVAC access room, 15' metal fixed ladder, the distance from the top rung to the top of the metal edge of the hatch was 20 inches exposing employees to falls of approximately 16 feet.