Violation Detail
Standard Cited: 19100119 F01 III B Process safety management of highly hazardous chemicals.
Inspection Nr: 1261126.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,934.00
Current Penalty: $12,934.00
Issuance Date: 03/01/2018
Nr Instances: 1
Nr Exposed: 418
Abatement Date: 04/17/2018
Gravity: 10
Report ID: 0729700
Contest Date:
Final Order: 03/27/2018
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/27/2018 | $12,934.00 | 04/17/2018 | Serious | |
| Penalty | Z: Issued | 03/01/2018 | $12,934.00 | 04/17/2018 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(f)(1)(iii)(B): Precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment; The employer is failing to protect employees from fire and explosion hazards while engaged in petroleum refining activities. This was most recently documented on or about September 4, 2017 at the HollyFrontier El Dorado Refining LLC, located at 1401 Douglas Road in El Dorado, Kansas. a) Employers standard operating procedures for B-2503 did not include precautions necessary to prevent exposure, including administrative controls, indicating that B-2503 was not permitted to exceed the alarm set point for upper firebox temperature. b) The operating practice of "bouncing the alarm" became a normal practice such that the furnace temperatures exceeded the upper firebox temperature (T125067) and the tube skin temperature (T125001) alarm limits on a regular/normal basis.
Translate