Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1256207.015
Citation: 01001
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $6,772.00
Current Penalty: $4,740.40
Issuance Date: 11/28/2017
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0523400
Contest Date:
Final Order: 12/08/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/08/2017 | $4,740.40 | Serious | ||
Penalty | Z: Issued | 11/28/2017 | $6,772.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.107(c)(6): Electrical wiring, motors, and other equipment outside of but within twenty (20) feet of any spray area, and not separated therefrom by partitions, produced sparks under normal operating conditions and did not otherwise conform to the provisions of subpart S of this part for Class I, Division 2 Hazardous Locations: (a) At the paint booth where the interior of the drums are coated the two electrical lights placed outside the booth were 19 inches and 32 1/2 inches from the booth opening. The electrical lights were not classified or listed for Class I, Division 2 Hazardous locations nor did they conform to electrical equipment for this Class 1, Division 2 area.