Violation Detail
Standard Cited: 19100119 E01 Process safety management of highly hazardous chemicals.
Inspection Nr: 1238280.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $9,778.00
Current Penalty: $9,778.00
Issuance Date: 09/20/2017
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 11/07/2017
Gravity: 5
Report ID: 0317500
Contest Date:
Final Order: 10/17/2017
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 09/20/2017 | $9,778.00 | 11/07/2017 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(e)(1): The process hazard analysis did not identify, evaluate, and address the control of the hazards involved in the process: (a) In the Facility, B-14 and B-10- On or about June 5, 2017, the employer did not evaluate the Rosedale filter system in the process hazard analysis (PHA) to identify the hazards related to the filter. The filter failed during the operation of Titan Step 3, allowing DCDMH to bypass the filter and enter the vacuum system and pump which caused the vacuum pump housing to explode, injuring three workers.
Translate