Violation Detail
Standard Cited: 19100119 D02 I D Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1194726.015
Citation: 01001
Citation Type: Serious
Abatement Date: 06/12/2017
Initial Penalty: $9,959.00
Current Penalty: $0.00
Issuance Date: 05/08/2017
Nr Instances: 1
Nr Exposed: 6
Related Event Code (REC):
Gravity: 5
Report ID: 0216000
Contest Date: 05/25/2017
Final Order: 02/07/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 02/07/2019 | $0.00 | 06/12/2017 | Serious | |
Penalty | C: Contested | 05/31/2017 | $9,959.00 | 06/12/2017 | Serious | |
Penalty | Z: Issued | 05/08/2017 | $9,959.00 | 06/12/2017 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(2)(i)(D): Information concerning the technology of the process did not include safe upper and lower limits for such items as temperatures, pressures, flows or compositions: a) Ammonia Refrigeration System - Covered Process: The employer's "Process Safety Information" document (pg. 12) did not contain accurate information in that it identified the maximum allowable working pressure (mawp) for Vogt Ice Makers 5, 6, 7, and 8 as 275 psig when the actual mawp was 200 psig as identified on the pressure vessel nameplates; on or about 12/19/16.