Violation Detail
Standard Cited: 19100159 C10 Automatic sprinkler systems.
Inspection Nr: 1192685.015
Citation: 01001
Citation Type: Other
Abatement Date: 01/12/2017 2
Initial Penalty: $8,017.00
Current Penalty: $5,000.00
Issuance Date: 01/06/2017
Nr Instances: 1
Nr Exposed: 15
Related Event Code (REC): C
Gravity:
Report ID: 0317000
Contest Date: 02/03/2017
Final Order: 02/13/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 04/21/2017 | $8,017.00 | 01/12/2017 | Serious | |
Penalty | F: Formal Settlement | 02/13/2017 | $5,000.00 | 01/12/2017 | Other | |
Penalty | Z: Issued | 01/06/2017 | $8,017.00 | 01/12/2017 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained. a) Jobsite: Lower level loading dock, back room storage area, racking system - The stored material, including the racking shelves, interfered with the sprinkler discharge pattern as they were spaced between 12 and 15 inches from the sprinklers. Observed on or about 11/21/16.