Violation Detail
Standard Cited: 19100106 D03 II A Flammable liquids.
This violation item has been deleted.
Inspection Nr: 1191889.015
Citation: 01001
Citation Type: Serious
Abatement Status:
Initial Penalty: $7,126.00
Current Penalty: $0.00
Issuance Date: 01/11/2017
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 02/13/2017
Gravity: 5
Report ID: 0213600
Contest Date: 01/30/2017
Final Order: 04/03/2017
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | J: ALJ Decision | 04/03/2017 | $0.00 | 02/13/2017 | Serious | |
| Penalty | C: Contested | 02/10/2017 | $7,126.00 | 02/13/2017 | Serious | |
| Penalty | Z: Issued | 01/11/2017 | $7,126.00 | 02/13/2017 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(d)(3)(ii)(a): Metal cabinet(s) were not deemed to be in compliance as they were not constructed with the bottom, top, door, and sides of cabinet at least No. 18 gage sheet iron and double walled with 1 1/2-inch air space; the joints riveted, welded, or made tight by some equally effective means; the door provided with a three-point lock; and/or the door sill raised at least 2 inches above the bottom of the cabinet: a) On or about 11/18/16 in the Bay area; employees were exposed to a fire hazard when approximately 104 containers of flammable stains and spray paints, such as but not limited to, Rust-oleum Spray paint, Rust-oleum Stain and Minwax Wood stain, were being stored in an ordinary metal cabinet labeled " Handyman Power Tools " ABATEMENT CERTIFICATION REQUIRED