Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1170480.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,329.00
Current Penalty: $6,884.34
Issuance Date: 10/18/2016
Nr Instances: 2
Nr Exposed: 50
Abatement Date: 11/21/2016
Gravity: 5
Report ID: 0729300
Contest Date:
Final Order: 11/10/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/10/2016 | $6,884.34 | 11/21/2016 | Serious | |
Penalty | Z: Issued | 10/18/2016 | $8,329.00 | 11/21/2016 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices(RAGAGEP). (a) At the time of the inspection, the machinery room ventilation did not meet the requirements of ANSI/IIAR 2-2008 section 13.3.8(b) for the volume of normal mechanical ventilation to limit the room temperature to 104 degrees F. An engineering study concluded that 189,436cfm was required and 158,800cfm exited. b) At the time of the inspection, three rework evaporator tanks did not have labels as required by ANSI/IIAR 2-2008 section 8..2.3.2(a). Without the required labels the employer was not able to determine if the pressure vessels were operating within the design parameters. Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citations.