Violation Detail
Standard Cited: 19100333 A01 Selection and use of work practices
Inspection Nr: 1158589.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,471.00
Current Penalty: $12,471.00
Issuance Date: 12/21/2016
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 01/19/2017
Gravity: 10
Report ID: 0214200
Contest Date: 01/13/2017
Final Order: 08/02/2019
Related Event Code (REC): A
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 08/02/2019 | $12,471.00 | 01/19/2017 | Serious | |
Penalty | C: Contested | 01/14/2017 | $12,471.00 | 01/19/2017 | Serious | |
Penalty | Z: Issued | 12/21/2016 | $12,471.00 | 01/19/2017 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de-energized before the employee worked on or was near to them: a) Facility General maintenance mechanics work on live 277 volt AC while changing ballasts for overhead fluorescent lights. On or about 06/26/16, a worker performing such operations received an electrical shock while working from an A frame ladder. The worker fell approximately 6 ft. to the floor below, striking his head and later died of his injuries.