Violation Detail
Standard Cited: 19100303 G01 II General.
Inspection Nr: 108646.015
Citation: 01001
Citation Type: Serious
Abatement Date: 11/27/2011 2
Initial Penalty: $4,250.00
Current Penalty: $4,250.00
Issuance Date: 11/22/2011
Nr Instances: 1
Nr Exposed: 3
Related Event Code (REC):
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 12/16/2011
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 11/22/2011 | $4,250.00 | 11/27/2011 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) On, 11/03/2011, at the workplace, in the Kitchen Area, an electrical supply box, had insufficient clearance between the front of the enclosure and the baking materials stored in front of it.