Violation Detail
Standard Cited: 19260404 B01 II Wiring design and protection.
Inspection Nr: 1015126.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,800.00
Current Penalty: $1,400.00
Issuance Date: 03/03/2015
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 03/27/2015
Gravity: 5
Report ID: 0316400
Contest Date:
Final Order: 03/24/2015
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/24/2015 | $1,400.00 | 03/27/2015 | Serious | |
| Penalty | Z: Issued | 03/03/2015 | $2,800.00 | 03/27/2015 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.404(b)(1)(ii): Where an assured equipment grounding program was not utilized, receptacles were not protected with ground-fault circuit-interrupters when on a two-wire, single-phase portable or vehicle-mounted generator rated more than 5kW, or where the circuit conductors of the generator were not insulated from the generator frame and all other grounded surfaces: a.) K & F Construction, Inc., Suncrest Village: On or about 12/18/14, the extension cords, being used to provide temporary power from the portable Honda Black Max 8750 Watt generator, to energize portable power tools, were not protected with ground fault circuit interrupters or an assured grounding program to protect employees from electrical shock hazards. ABATEMENT CERTIFICATION REQUIRED FOR THIS ITEM